Johannesburg 1 Data Center
With a total of 6,000 sqm of IT space and a maximum of 12 MW once fully built out, Johannesburg 1 will offer complete solutions for housing your IT and network systems in a secure, high availability environment. We provide you with the best possible physical and technical infrastructure supported by N+1 UPS systems, N+1 generator backup, as well as highly redundant cooling systems. Our data center will hold multiple certifications and will be connected to the major Internet Service Providers NAP Africa and JINX.
Johannesburg 1 overview
- 6,000 sqm of IT space
- 12 MW of critical IT load
- Fully-fitted colocation space and private suites
- Shell and core areas available
- Multi Service Interconnection Platform
- Cross Connects
- Technology Experience Lab to test and validate new technologies
Take a look inside Johannesburg 1
Speak to one of our experts
Johannesburg 1 specifications
Power
- On-site substation delivering 20 MVA of power
- Maximum client IT load of 12 MW
- Average power density of 2.0 kW/sqm
- Power supply at 20 kV level
- All IT racks supplied with two separate UPS systems (A- and B-supply) with N+1 redundancy
- Redundantly designed emergency power system with diesel generators N+1
Security
- 24/7 Security Operations Center and remote Service Control Center
- Redundant monitoring of all critical functions underpinned by standardized security processes and the multi level security zone principle, secures the rental area and the technical operation
- Site perimeter fence to be 2,700 mm high ClearVu or similar fence, with extended post to 3,000 mm accommodating an electric fence
Connectivity
- Carrier-neutral
- Carrier mix from global tier 1 supplier to regional supplier
- Inter data center connectivity between NTT data centers for geo-redundant solutions
- Multi Service Interconnection Platform to connect our clients to major cloud service providers
- Redundant Carrier-Meet-Me-Rooms
Cooling
- Chilled water data suite cooling with aircooled free-cooling chiller systems with a minimum of N+1 redundancy and supplemental adiabatic system for efficiency
- Concurrently maintainable AHUs providing fresh air pressurization and humidity control to data suites
- Chilled water cooling to MMR and to electrical plant rooms (N+1)